Input/Output (IO) Module CFLink Protocol

The following documentation describes the CFLink protocol for modular IO devices.

Common Definitions

Port Modes

Throughout this document, the configuration and status of each port <MODE> and it's associated <STATE> refers to the following possibilities:

  • <MODE> = Single uppercase char:
    • D = Dry contact input (Default mode), <STATE> = 0 for Open, 1 for Closed.
    • R = Resistance reading input, <STATE> = 000-100 (0 to 10,000 Ohms in 100 Ohm increments)
    • A = Analog Voltage reading input, <STATE> = 000-100 (00.0 to 10.0 Volts DC in 0.1 Volt increments)
    • V = Digital Voltage reading input, <STATE> = 0 for voltage below threshold, 1 for voltage equal to or above threshold
    • S = Video Sensing input, <STATE> = 0 for no video sensed, 1 for video sensed.
    • E = External relay control output, 0-24V DC (external power supply required), <STATE> = 0 for OFF, 1 for ON.
    • L = LED output (1mA), <STATE> = 0 for OFF, 1 for ON.

Queries

STA - Query Status

The STA (Status) query returns the status of all IO ports in a single module.

Data


> [F2]<ID>[F3]QIOXSTA[F4]<MODULE>[F5][F5]

  • <MODULE> = The module number to request the status of. 2 chars, uppercase 'M' followed by the module number.
    • eg. M1 = Module 1, M4 = Module 4.

Reply

< [F2]<ID>[F3]RIOXSTA[F4]<MODULE>|<IODATA>[F5][F5]

  • <IODATA> = For each IO port in the module, the port status is returned in P##:<MODE>:<STATE> format.
    • <MODE> = Single uppercase char. Refer to Common Definitions - Port Modes for more information on the possible modes and states.

Example

// Query the state of IO ports in Module 2 of a modular device on CFLink ID [04]
> [F2][04][F3]QIOXSTA[F4]M2[F5][F5]
// Reply, Module has 8 IO ports
< [F2][04][F3]RIOXSTA[F4]M2|P01:D:0|P02:D:1|P03:R:010|P04:V:125|P05:E:0|P06:L:1|P07:D:0|P08:S:1[F5][F5]
// Port 1 = Dry contact, Off
// Port 2 = Dry contact, On
// Port 3 = Resistence, 1000 Ohm reading
// Port 4 = Voltage, 12.5V reading
// Port 5 = External relay control, Off
// Port 6 = LED ouput, On
// Port 7 = Dry contact, Off
// Port 8 = Video Sense, video signal present.

Error

  • 004 = Invalid Module Number

PRT - Query Port Settings

The PRT (Port) query returns the configuration for all IO ports in a single module.

Data

> [F2]<ID>[F3]QIOXPRT[F4]<MODULE>[F5][F5]

  • <MODULE> = The module number to request the port configuration of. 2 chars, uppercase 'M' followed by the module number.
    • eg. M1 = Module 1, M4 = Module 4.

Reply

< [F2]<ID>[F3]RIOXPRT[F4]<MODULE>|<PORT_CONFIG>[F5][F5]

  • <PORT_CONFIG> = For each IO port in the module, the port configuration is returned in P##:<MODE>:<MIN_CHANGE>:<POWER_ON_STATE> format.
    • <MODE> = Single uppercase char. Refer to Common Definitions - Port Modes for more information on the possible modes and states.
    • <MIN_CHANGE> = The minimum change the port must read before sending a notification message.
      • 0 means reporting on change is disabled, and on change reporting can be disabled on a module level as well.
      • 0 (zero) is always returned for ports in modes D, E and L.
    • <POWERONSTATE> = The state the port will be in when the unit is powered up.
      • 0 (zero) is always returned for ports in modes D, R and V.

Example

// Query the configuration of IO ports in Module 1 of a modular device on CFLink ID [04]
> [F2][04][F3]QIOXPRT[F4]M1[F5][F5]
// Reply, Module has 8 IO ports
< [F2][04][F3]RIOXPRT[F4]M1|P01:D:0:0|P02:D:0:0|P03:R:15:0|P04:V:12:0|P05:E:0:0|P06:L:0:1|P07:D:0:0|P08:D:0:0[F5][F5]
// Port 1 = Dry contact
// Port 2 = Dry contact
// Port 3 = Resistence, 1500 Ohm minimum change
// Port 4 = Voltage, 1.2 V minimum change
// Port 5 = External relay control, Power On State = Off
// Port 6 = LED ouput, Power On State = On
// Port 7 = Dry contact
// Port 8 = Dry contact

Error

  • 004 = Invalid Module Number

CFG - Query Configuration

The CFG (Configuration) query returns the configuration of a single IO module.

Data

> [F2]<ID>[F3]QIOXCFG[F4]<MODULE>[F5][F5]

  • <MODULE> = The module number to request the module configuration of. 2 chars, uppercase 'M' followed by the module number.
    • eg. M1 = Module 1, M4 = Module 4.

Reply

< [F2]<ID>[F3]RIOXCFG[F4]<MODULE>:<ENABLED>:<REPORT_ON_CHANGE>:<REPORT_INTERVAL>[F5][F5]

  • <ENABLED> = This reports if the module is enabled or disabled for input reading (and hence disable reporting notifications). Disabling a module is great for trouble shooting to silence the module on the CFLink bus without having to physically unplug it. Single digit, 0 = disabled, 1 = enabled.
  • <REPORTONCHANGE> = This reports if the module allows for any IO ports to force a status notification when its input value changes.
    • The minimum change setting for a port must be reached before any notification will be sent.
    • If this is disabled, all port minimum change settings will be ignored.
    • 0 = Disable report on change, 1 = Enable report on change.
  • <REPORT_INTERVAL> = The interval at which the module will report it's status. 5 digits, representing 0 - 9999.9 seconds (100ms increments).
    • 00000 = Module will not report on any interval (disabled).
    • 00001 = Module will report every 0000.1 seconds (100ms).
    • 00600 = Module will report every minute.
    • 36000 = Module will report every hour.
    • 99999 = Module will report every 9999.9 seconds (2h46m39s900ms or 9,999,900ms)
    • There is a great online calculator here for converting this value into h:m:s (simply enter ::9999.9 to see the max range for example)