hardware:din-ry8-n [2023/03/06 13:30]
terrylau
hardware:din-ry8-n [2023/03/06 13:34] (current)
terrylau
Line 4: Line 4:
  
  
-===== REAL-TIME LOAD DETECTION ​=====+===== Real-Time Load Detection ​=====
  
 A unique feature which allows each of the load states to be detected when wired as per our wiring guidelines. This allows 2-way mechanical switches to be used in conjunction with this unit where both units act as a traditional A unique feature which allows each of the load states to be detected when wired as per our wiring guidelines. This allows 2-way mechanical switches to be used in conjunction with this unit where both units act as a traditional
Line 11: Line 11:
 The unique load detection also allows the state of each load to be detected, and through our protocol, allows discrete on and off commands to be issued which automatically evaluates the state of the load first before deciding whether or not the relay needs to be switched. The unique load detection also allows the state of each load to be detected, and through our protocol, allows discrete on and off commands to be issued which automatically evaluates the state of the load first before deciding whether or not the relay needs to be switched.
  
-===== MACROS/RULES =====+===== Macros/Rules =====
  
 On-board rules engine allows macros to be fired when events such as dry contact or load status changes are detected. Macros can be used to control multiple DIN-RY family units in the looping RS232 or RS485 chain or to send custom messages to control systems via the RS232 and RS485 ports. Programming is completed using a cross-platform (Windows & Mac) application,​ connected via either RS232, RS485, USB or Ethernet when using an Ethernet to serial converter such as the CommandFusion LAN Bridge or Solo products. On-board rules engine allows macros to be fired when events such as dry contact or load status changes are detected. Macros can be used to control multiple DIN-RY family units in the looping RS232 or RS485 chain or to send custom messages to control systems via the RS232 and RS485 ports. Programming is completed using a cross-platform (Windows & Mac) application,​ connected via either RS232, RS485, USB or Ethernet when using an Ethernet to serial converter such as the CommandFusion LAN Bridge or Solo products.
  
-===== CONNECTIVITY ​=====+===== Connectivity ​=====
  
 Relay Outputs - 8 x latching relay switching outputs; 8 x 3-pin fixed-mount terminals blocks with L1, L2 and common; Relay Rating: 16 Amps resistive at 240 VAC. Relay Outputs - 8 x latching relay switching outputs; 8 x 3-pin fixed-mount terminals blocks with L1, L2 and common; Relay Rating: 16 Amps resistive at 240 VAC.
Line 24: Line 24:
 DC Power - Looping IN and OUT DC power ports. 2 x detachable 2-pin 3.5mm terminal blocks. Accepts 12-24VDC DC Power - Looping IN and OUT DC power ports. 2 x detachable 2-pin 3.5mm terminal blocks. Accepts 12-24VDC
  
-===== POWER =====+===== Power =====
  
 AC Input - 220-250VAC Neutral line for load detection. AC Input - 220-250VAC Neutral line for load detection.
Line 30: Line 30:
 AC (load monitoring) -  3.2W for 250VAC (max) AC (load monitoring) -  3.2W for 250VAC (max)
  
-===== FRONT PANEL =====+===== Front Panel =====
  
 8 x yellow LEDs for status indication and miniature push buttons for toggling relay outputs. 8 x yellow LEDs for status indication and miniature push buttons for toggling relay outputs.
Line 38: Line 38:
 RS485 - 1 x yellow LED indicating RS485 serial traffic. RS485 - 1 x yellow LED indicating RS485 serial traffic.
 Unit ID - 2 x 7-segment red LED display shows the unit ID on the looping bus. Blinks during setup mode. Unit ID - 2 x 7-segment red LED display shows the unit ID on the looping bus. Blinks during setup mode.
 +Up/Down - 2 x miniature recessed push buttons used to change the unit ID when in setup mode.
 +Setup - 1 x miniature recessed push button used for entering setup mode to allow unit ID changes via up/down buttons.
 +Reset - 1 x miniature recessed push button to perform a soft reboot.
 +Dry Contact Inputs - 8 x yellow LEDs indicating the state of the dry contact inputs.
 +
 +
 +===== Physical =====
 +Enclosure Polycarbonate with light grey finish and black fascia, occupies
 +9 DIN module spaces, utilises 35mm DIN EN 60715 rail mount.
 +Height 61mm (2.40in)
 +Width 161.6mm (6.36in)
 +Depth 89.7mm (3.53in)
 +Weight 0.412kg (0.9lbs), Shipping 0.55kg (1.21lbs)
 +Temperature 0°C to 50°C (32°F to 122°F)
 +Humidity 10% to 90% RH, non-condensing
 +Certification FCC, CE, C-Tick
  
hardware/din-ry8-n.txt · Last modified: 2023/03/06 13:34 by terrylau